[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"$fULvbunqC26TZbtK5hrjt4NLwi8kmsyjTbQm2X473Kw0":3},{"article":4,"iocs":38,"watch_terms":56},{"id":5,"title":6,"slug":7,"summary":8,"ai_summary":9,"brief":10,"full_text":11,"url":12,"image_url":13,"published_at":14,"ingested_at":15,"relevance_score":16,"entities":17,"category_id":18,"category":19,"article_tags":22},"f2d36317-5bf7-41e3-8872-d2d507d02f5f","Schneider Electric Plant iT\u002FBrewmaxx","schneider-electric-plant-it-brewmaxx","View CSAF Summary Successful exploitation of these vulnerabilities could risk privilege escalation, which could result in remote code execution. The following versions of Schneider Electric Plant iT\u002FBrewmaxx are affected: Plant iT\u002FBrewmaxx 9.60_and_above (CVE-2025-49844, CVE-2025-46817, CVE-2025-46818, CVE-2025-46819) CVSS Vendor Equipment Vulnerabilities v3 9.9 Schneider Electric Schneider Electric Plant iT\u002FBrewmaxx Use After Free, Integer Overflow or Wraparound, Improper Control of Generation of Code ('Code Injection') Background Critical Infrastructure Sectors: Energy, Critical Manufacturing, Commercial Facilities Countries\u002FAreas Deployed: Worldwide Company Headquarters Location: France Vulnerabilities Expand All + CVE-2025-49844 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to manipulate the garbage collector, trigger a use-after-free, and potentially lead to remote code execution. View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor: Schneider Electric Product Version: Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status: known_affected Remediations Mitigation Schneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: Mitigation Install Patch ProLeiT-2025-001 via ProLeiT Support https:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F Mitigation After installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality Mitigation Force usage of secure Redis configuration templates in system settings as documented in the patch manual Mitigation Restart all patched servers and workstations Mitigation Schneider Electric strongly recommends the following industry cybersecurity best practices. Mitigation Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Mitigation Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Mitigation Place all controllers in locked cabinets and never leave them in the \"Program\" mode. Mitigation Never connect programming software to any network other than the network intended for that device. Mitigation Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Mitigation Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Mitigation Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. Mitigation When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. Mitigation For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fix For more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\" https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.9 CRITICAL CVSS:3.1\u002FAV:N\u002FAC:L\u002FPR:L\u002FUI:N\u002FS:C\u002FC:H\u002FI:H\u002FA:H CVE-2025-46817 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to cause an integer overflow and potentially lead to remote code execution View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor: Schneider Electric Product Version: Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status: known_affected Remediations Mitigation Schneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: Mitigation Install Patch ProLeiT-2025-001 via ProLeiT Support https:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F Mitigation After installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality Mitigation Force usage of secure Redis configuration templates in system settings as documented in the patch manual Mitigation Restart all patched servers and workstations Mitigation Schneider Electric strongly recommends the following industry cybersecurity best practices. Mitigation Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Mitigation Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Mitigation Place all controllers in locked cabinets and never leave them in the \"Program\" mode. Mitigation Never connect programming software to any network other than the network intended for that device. Mitigation Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Mitigation Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Mitigation Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. Mitigation When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. Mitigation For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fix For more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\" https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 7 HIGH CVSS:3.1\u002FAV:L\u002FAC:H\u002FPR:L\u002FUI:N\u002FS:U\u002FC:H\u002FI:H\u002FA:H CVE-2025-46818 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to manipulate different LUA objects and potentially run their own code in the context of another user. View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor: Schneider Electric Product Version: Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status: known_affected Remediations Mitigation Schneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: Mitigation Install Patch ProLeiT-2025-001 via ProLeiT Support https:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F Mitigation After installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality Mitigation Force usage of secure Redis configuration templates in system settings as documented in the patch manual Mitigation Restart all patched servers and workstations Mitigation Schneider Electric strongly recommends the following industry cybersecurity best practices. Mitigation Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Mitigation Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Mitigation Place all controllers in locked cabinets and never leave them in the \"Program\" mode. Mitigation Never connect programming software to any network other than the network intended for that device. Mitigation Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Mitigation Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Mitigation Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. Mitigation When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. Mitigation For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fix For more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\" https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-94 Improper Control of Generation of Code ('Code Injection') Metrics CVSS Version Base Score Base Severity Vector String 3.1 6 MEDIUM CVSS:3.1\u002FAV:L\u002FAC:H\u002FPR:L\u002FUI:R\u002FS:U\u002FC:H\u002FI:H\u002FA:N CVE-2025-46819 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted LUA script to read out-of-bound data or crash the server and subsequent denial of service. View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor: Schneider Electric Product Version: Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status: known_affected Remediations Mitigation Schneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: Mitigation Install Patch ProLeiT-2025-001 via ProLeiT Support https:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F Mitigation After installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality Mitigation Force usage of secure Redis configuration templates in system settings as documented in the patch manual Mitigation Restart all patched servers and workstations Mitigation Schneider Electric strongly recommends the following industry cybersecurity best practices. Mitigation Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Mitigation Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Mitigation Place all controllers in locked cabinets and never leave them in the \"Program\" mode. Mitigation Never connect programming software to any network other than the network intended for that device. Mitigation Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Mitigation Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Mitigation Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. Mitigation When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. Mitigation For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fix For more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\" https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.3 MEDIUM CVSS:3.1\u002FAV:L\u002FAC:H\u002FPR:L\u002FUI:N\u002FS:U\u002FC:H\u002FI:N\u002FA:H Acknowledgments Schneider Electric reported these vulnerabilities to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https:\u002F\u002Fwww.cisa.gov\u002Fnotification) and this Privacy & Use policy (https:\u002F\u002Fwww.cisa.gov\u002Fprivacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and\u002For systems, ensuring they are not accessible from the Internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov\u002Fics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov\u002Fics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-03-24 Date Revision Summary 2026-03-24 1 Initial Republication of SEVD-2026-013-01 Legal Notice and Terms of Use","Schneider Electric disclosed four critical vulnerabilities (CVE-2025-49844, CVE-2025-46817, CVE-2025-46818, CVE-2025-46819) in Plant iT\u002FBrewmaxx 9.60 and above, stemming from insecure Redis implementations in versions 8.2.1 and below. Authenticated attackers can exploit specially crafted Lua scripts to trigger use-after-free, integer overflow, code injection, and denial-of-service conditions, potentially achieving remote code execution. Schneider Electric released patch ProLeiT-2025-001 and recommends immediate mitigation including disabling Redis eval commands and enforcing secure configuration templates.","Schneider Electric Plant iT\u002FBrewmaxx versions 9.60+ vulnerable to Redis flaws enabling RCE and DoS.","ICS Advisory Schneider Electric Plant iT\u002FBrewmaxx Release DateMarch 24, 2026 Alert CodeICSA-26-083-03 Related topics: Industrial Control System Vulnerabilities, Industrial Control Systems View CSAF Summary Successful exploitation of these vulnerabilities could risk privilege escalation, which could result in remote code execution. The following versions of Schneider Electric Plant iT\u002FBrewmaxx are affected: Plant iT\u002FBrewmaxx 9.60_and_above (CVE-2025-49844, CVE-2025-46817, CVE-2025-46818, CVE-2025-46819) CVSS Vendor Equipment Vulnerabilities v3 9.9 Schneider Electric Schneider Electric Plant iT\u002FBrewmaxx Use After Free, Integer Overflow or Wraparound, Improper Control of Generation of Code ('Code Injection') Background Critical Infrastructure Sectors: Energy, Critical Manufacturing, Commercial Facilities Countries\u002FAreas Deployed: Worldwide Company Headquarters Location: France Vulnerabilities Expand All + CVE-2025-49844 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to manipulate the garbage collector, trigger a use-after-free, and potentially lead to remote code execution. View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor:Schneider Electric Product Version:Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status:known_affected Remediations MitigationSchneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: MitigationInstall Patch ProLeiT-2025-001 via ProLeiT Supporthttps:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F MitigationAfter installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality MitigationForce usage of secure Redis configuration templates in system settings as documented in the patch manual MitigationRestart all patched servers and workstations MitigationSchneider Electric strongly recommends the following industry cybersecurity best practices. MitigationLocate control and safety system networks and remote devices behind firewalls and isolate them from the business network. MitigationInstall physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. MitigationPlace all controllers in locked cabinets and never leave them in the \"Program\" mode. MitigationNever connect programming software to any network other than the network intended for that device. MitigationScan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. MitigationNever allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. MitigationMinimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. MitigationWhen remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. MitigationFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fixFor more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\"https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-416 Use After Free Metrics CVSS Version Base Score Base Severity Vector String 3.1 9.9 CRITICAL CVSS:3.1\u002FAV:N\u002FAC:L\u002FPR:L\u002FUI:N\u002FS:C\u002FC:H\u002FI:H\u002FA:H CVE-2025-46817 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to cause an integer overflow and potentially lead to remote code execution View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor:Schneider Electric Product Version:Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status:known_affected Remediations MitigationSchneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: MitigationInstall Patch ProLeiT-2025-001 via ProLeiT Supporthttps:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F MitigationAfter installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality MitigationForce usage of secure Redis configuration templates in system settings as documented in the patch manual MitigationRestart all patched servers and workstations MitigationSchneider Electric strongly recommends the following industry cybersecurity best practices. MitigationLocate control and safety system networks and remote devices behind firewalls and isolate them from the business network. MitigationInstall physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. MitigationPlace all controllers in locked cabinets and never leave them in the \"Program\" mode. MitigationNever connect programming software to any network other than the network intended for that device. MitigationScan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. MitigationNever allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. MitigationMinimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. MitigationWhen remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. MitigationFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.https:\u002F\u002Fwww.se.com\u002Fus\u002Fen\u002Fdownload\u002Fdocument\u002F7EN52-0390\u002F Vendor fixFor more information, see Schneider Electric security notification \"SEVD-2026-013-01 Multiple Third-Party Vulnerabilities on ProLeiT Plant iT\u002FBrewmaxx\"https:\u002F\u002Fdownload.schneider-electric.com\u002Ffiles?p_Doc_Ref=SEVD-2026-013-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-013-01.pdf Relevant CWE: CWE-190 Integer Overflow or Wraparound Metrics CVSS Version Base Score Base Severity Vector String 3.1 7 HIGH CVSS:3.1\u002FAV:L\u002FAC:H\u002FPR:L\u002FUI:N\u002FS:U\u002FC:H\u002FI:H\u002FA:H CVE-2025-46818 The affected product uses Redis, an open-source, in-memory database. Versions 8.2.1 and below allow an authenticated user to use a specially crafted Lua script to manipulate different LUA objects and potentially run their own code in the context of another user. View CVE Details Affected Products Schneider Electric Plant iT\u002FBrewmaxx Vendor:Schneider Electric Product Version:Schneider Electric Plant iT\u002FBrewmaxx: 9.60_and_above Product Status:known_affected Remediations MitigationSchneider Electric recommends users immediately apply the following mitigations to reduce the risk of exploit: MitigationInstall Patch ProLeiT-2025-001 via ProLeiT Supporthttps:\u002F\u002Fwww.proleit.com\u002Fsupport\u002F MitigationAfter installing ProLeiT-2025-001, disable the eval commands in Redis on the application server, VisuHub, engineering workstations, and workstations with emergency mode functionality MitigationForce usage of secure Redis config","https:\u002F\u002Fwww.cisa.gov\u002Fnews-events\u002Fics-advisories\u002Ficsa-26-083-03",null,"2026-03-24T12:00:00+00:00","2026-03-24T17:00:17.361995+00:00",9,[],"80544778-fabb-4dcd-aa35-17492e5dcf4f",{"id":18,"icon":13,"name":20,"slug":21},"Vulnerabilities","vulnerabilities",[23,28,33],{"category":24},{"id":25,"icon":13,"name":26,"slug":27},"26b0b636-0e31-4db1-bffb-61bdf9f20a58","Supply Chain","supply-chain",{"category":29},{"id":30,"icon":13,"name":31,"slug":32},"ade75414-7914-4e23-a450-48b64546ee70","Open Source","open-source",{"category":34},{"id":35,"icon":13,"name":36,"slug":37},"d6f63bb8-0801-486a-be7f-171400700454","IoT\u002FOT","iot-ot",[39,43,46,49,52],{"type":40,"value":41,"context":42},"cve","CVE-2025-49844","Redis use-after-free in Plant iT\u002FBrewmaxx leading to RCE; CVSS 9.9 CRITICAL",{"type":40,"value":44,"context":45},"CVE-2025-46817","Redis integer overflow in Plant iT\u002FBrewmaxx leading to RCE; CVSS 7.0 HIGH",{"type":40,"value":47,"context":48},"CVE-2025-46818","Redis code injection via Lua script manipulation in Plant iT\u002FBrewmaxx; CVSS 6.0 MEDIUM",{"type":40,"value":50,"context":51},"CVE-2025-46819","Redis out-of-bounds read and DoS via Lua script in Plant iT\u002FBrewmaxx; CVSS 6.3 MEDIUM",{"type":53,"value":54,"context":55},"malware","ProLeiT-2025-001","Security patch for Schneider Electric Plant iT\u002FBrewmaxx; disables Redis eval commands",[]]