Back to Feed
VulnerabilitiesJul 21, 2026

Rockwell Automation 1734 POINT I/O

Rockwell Automation 1734 POINT I/O module vulnerable to denial-of-service.

Summary

A denial-of-service vulnerability has been identified in Rockwell Automation's 1734 POINT I/O module, specifically affecting version 3.023. Exploitation of this flaw, stemming from improper handling of crafted CIP messages, could cause the module to enter a faulted state requiring a restart. Rockwell Automation recommends migrating to the 5034-OB8 model or implementing security best practices to mitigate the risk.

Full text

ICS Advisory Rockwell Automation 1734 POINT I/O Release DateJuly 21, 2026 Alert CodeICSA-26-202-09 Related topics: Industrial Control System Vulnerabilities , Industrial Control Systems View CSAF Summary Successful exploitation of this vulnerability could allow for an attacker to cause a denial-of-service condition on the product. The following versions of Rockwell Automation 1734 POINT I/O are affected: 1734 POINT I/O 3.023 CVSS Vendor Equipment Vulnerabilities v3 7.5 Rockwell Automation Rockwell Automation 1734 POINT I/O Allocation of Resources Without Limits or Throttling Background Critical Infrastructure Sectors: Critical Manufacturing Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2026-10573 A denial-of-service security issue exists in 1734 POINT I/O module. The security issue stems from improper handling of crafted CIP messages, which can cause the module to enter a faulted state. A restart is required to recover. View CVE Details Affected Products Rockwell Automation 1734 POINT I/O Vendor:Rockwell Automation Product Version:Rockwell Automation 1734 POINT I/O: 3.023 Product Status:known_affected Remediations MitigationRockwell Automation recommends users are to migrate to 5034-OB8. MitigationCustomers using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell Automation's security best practices (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight).https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight MitigationFor more information, see Rockwell Automation Security Advisories: https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html.https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html Relevant CWE: CWE-770 Allocation of Resources Without Limits or Throttling Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H 4.0 8.7 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N Acknowledgments Rockwell Automation reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. Revision History Initial Release Date: 2026-07-21 Date Revision Summary 2026-07-21 1 Initial Republication of Rockwell Automation Security Advisory Legal Notice and Terms of Use This product is provided subject to this Notification and this Privacy & Use policy. Vendor Rockwell Automation Tags Sector: Critical Manufacturing Sector Topics: Industrial Control System Vulnerabilities, Industrial Control Systems Please share your thoughts We recently updated our anonymous product survey; we welcome your feedback. Related Advisories Jul 21, 2026 ICS Advisory | ICSA-26-202-01 Tycon Systems TPDIN-Monitor-WEB2 Jul 21, 2026 ICS Advisory | ICSA-26-202-10 Rockwell Automation Studio 5000 Logix Designer Jul 21, 2026 ICS Advisory | ICSA-26-202-02 Siemens RUGGEDCOM APE1808 with Palo Alto Networks Virtual NGFW Jul 21, 2026 ICS Advisory | ICSA-26-202-04 Siemens SIDIS Secured SmartPlug

Indicators of Compromise

  • cve — CVE-2026-10573

Entities

1734 POINT I/O (product)Rockwell Automation (vendor)5034-OB8 (product)