Back to Feed
VulnerabilitiesSep 17, 2026

Schneider Electric Modicon M340 Controller and Communication Modules

Schneider Electric Modicon M340 controller and communication modules vulnerable to DoS via crafted FTP command.

Summary

Schneider Electric has identified a Denial of Service vulnerability in its Modicon M340 controller and communication modules. The vulnerability, identified as CVE-2025-6625, stems from improper input validation and can be exploited by sending a specifically crafted FTP command. Successful exploitation could lead to the unavailability of the affected devices, impacting critical infrastructure sectors.

Full text

ICS Advisory Schneider Electric Modicon M340 Controller and Communication Modules Release DateSeptember 17, 2026 Alert CodeICSA-26-260-04 Related topics: Industrial Control System Vulnerabilities , Industrial Control Systems View CSAF Summary Schneider Electric is aware of a vulnerability in its Modicon M340 https://www.se.com/ww/en/product-range/1468-modicon-m340-pac/, BMXNOR0200H https://www.se.com/us/en/product/BMXNOR0200H/communication-module-modicon-m340-iec-608705101-104-dnp3-for-severe-environments/: Modicon M340 X80 Ethernet Communication Modules, BMXNGD0100 https://www.se.com/us/en/product/BMXNGD0100/communication-module-modicon-m580-global-data-service/: M580 Global Data module, BMXNOC0401 https://www.se.com/us/en/product/BMXNOC0401/network-module-modicon-m340-ethernet-ip-and-modbus-tcp-4-x-rj45/?pageType=product&sourceId=BMXNOC0401: Modicon M340 X80 Ethernet Communication modules, BMXNOE0100 https://www.se.com/ww/en/product/BMXNOE0100/network-module-modicon-m340-modbus-tcp-1-x-rj45-flash-memory-card/?pageType=product&sourceId=BMXNOE0100: Modbus/TCP Ethernet Modicon M340 module, BMXNOE0110 https://www.se.com/ww/en/product/BMXNOE0110/ethernet-tcp-ip-network-module-modicon-m340-automation-platform-flash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/: Modbus/TCP Ethernet Modicon M340 FactoryCast module product(s). Failure to apply the fix provided below may risk Denial Of Service attack, which could result in the unavailability of the devices. The following versions of Schneider Electric Modicon M340 Controller and Communication Modules are affected: Schneider Electric Ethernet/Serial RTU Module: vers:generic/<SV1.7_IR27 Schneider Electric M580 Global Data module: vers:all/* Schneider Electric Ethernet / Serial RTU Module: vers:all/* Schneider Electric Modbus/TCP Ethernet Modicon M340 module: vers:intdot/<3.60 Schneider Electric Modbus/TCP Ethernet Modicon M340 FactoryCast module: vers:intdot/<6.80 Schneider Electric Modicon M340 Firmware Versions prior to SV3.70 installed on Modicon M340 Controller: All versions CVSS Vendor Equipment Vulnerabilities v3 7.5 Schneider Electric Schneider Electric Modicon M340 Controller and Communication Modules Improper Input Validation Background Critical Infrastructure Sectors: Chemical, Commercial Facilities, Critical Manufacturing, Energy, Water and Wastewater Countries/Areas Deployed: Worldwide Company Headquarters Location: France Vulnerabilities Expand All + CVE-2025-6625 CWE-20: Improper Input Validation vulnerability exists that could cause a Denial Of Service when specific crafted FTP command is sent to the device. View CVE Details Affected Products Schneider Electric Modicon M340 Controller and Communication Modules Vendor:Schneider Electric Product Version:Ethernet / Serial RTU Module All versions, M580 Global Data module All versions, Modicon M340 X80 Ethernet Communication modules All versions, Modbus/TCP Ethernet Modicon M340 module Versions prior to 3.60, Modbus/TCP Ethernet Modicon M340 FactoryCast module Versions prior to 6.80 Product Status:fixed, known_affected Remediations Vendor fixVersion 3.60 of BMXNOE0100 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOE0100/network-module-modicon-m340-modbus-tcp-1-x-rj45-flash-memory-card/ Reboot is needed to complete the firmware upgrade Vendor fixVersion 6.80 of BMXNOE0110 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOE0110/ethernet-tcp-ip-network-module-modicon-m340-automation-platform-flash-memory-card-internal-ram-16-mb-1-x-rj45-10-100/ Reboot is needed to complete the firmware upgrade Vendor fixVersion SV3.70 of Modicon M340 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware Vendor fixVersion SV1.7 IR27 of BMXNOR0200H includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product/BMXNOR0200H/ethernet-serial-rtu-module-2-x-rj45/ MitigationIf customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: FTP service is disabled by default. Ensure to disable FTP service when not in use. Setup network segmentation and implement a firewall to block all unauthorized access to ports 21/FTP. Use VPN (Virtual Private Networks) tunnels if remote access is required. MitigationSchneider Electric is establishing a remediation plan for all future versions of: Modicon M340 BMXNOR0200H BMXNGD0100 BMXNOC401 Schneider Electric will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: FTP service is disabled by default. Ensure to disable FTP service when not in use. Setup network segmentation and implement a firewall to block all unauthorized access to ports 21/FTP. Use VPN (Virtual Private Networks) tunnels if remote access is required. Mitigation For more information see the associated Schneider Electric security advisory Modicon M340 Controller and Communication Modules - SEVD-2025-224-05 CSAF Version, Modicon M340 Controller and Communication Modules - SEVD-2025-224-05 PDF Version. Relevant CWE: CWE-20 Improper Input Validation Metrics CVSS Version Base Score Base Severity Vector String 3.1 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H Acknowledgments Schneider Electric CPCERT reported this vulnerability to CISA. General Security Recommendations We strongly recommend the following industry cybersecurity best practices. Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Place all controllers in locked cabinets and never leave them in the “Program” mode. Never connect programming software to any network other than the network intended for that device. Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. For More Information This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp LEGAL DISCLAIMER THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-

Indicators of Compromise

  • cve — CVE-2025-6625

Entities

Modicon M340 Controller (product)Modicon M340 Communication Modules (product)Schneider Electric (vendor)FTP (technology)