Summary
Schneider Electric has identified a vulnerability in its SCADAPack x70 series of Remote Terminal Units (RTUs). This flaw, tracked as CVE-2026-81861, could allow unauthorized access to RTU configurations, potentially leading to a loss of confidentiality. The vulnerability affects various SCADAPack models, and while a CVSS score of 6.5 (Medium) is assigned, the company recommends implementing Role-Based Access Control (RBAC) and network segmentation as mitigations.
Full text
ICS Advisory Schneider Electric SCADAPack x70 Products Release DateSeptember 15, 2026 Alert CodeICSA-26-258-04 Related topics: Industrial Control System Vulnerabilities , Industrial Control Systems View CSAF Summary Schneider Electric is aware of a vulnerability in its SCADAPack x70 products. The SCADAPack 47x, SCADAPack 47xi, SCADAPack 47xd, SCADAPack 470R and SCADAPack 57x products are Remote Terminal Units that provide communication capabilities for remote monitoring and control. Failure to apply the mitigations provided below may increase the risk of unauthorized access to RTU configuration through the Secure Lock functionality, potentially resulting in a loss of confidentiality. The following versions of Schneider Electric SCADAPack x70 Products are affected: SCADAPack 47x vers:all/* (CVE-2026-81861) SCADAPack 47xi vers:all/* (CVE-2026-81861) SCADAPack 47xd vers:all/* (CVE-2026-81861) SCADAPack 470R vers:all/* (CVE-2026-81861) SCADAPack 57x vers:all/* (CVE-2026-81861) SCADAPack 3xx vers:all/* (CVE-2026-81861) SCADAPack 32 vers:all/* (CVE-2026-81861) CVSS Vendor Equipment Vulnerabilities v3 6.5 Schneider Electric Schneider Electric SCADAPack x70 Products Insufficiently Protected Credentials Background Critical Infrastructure Sectors: Critical Manufacturing, Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: France Vulnerabilities Expand All + CVE-2026-81861 There is an insufficiently protected credentials vulnerability that could result in exposure of authentication information and unauthorized access to RTU functionality. View CVE Details Affected Products Schneider Electric SCADAPack x70 Products Vendor:Schneider Electric Product Version:SCADAPack 47x, SCADAPack 47xi, SCADAPack 47xd, SCADAPack 470R, SCADAPack 57x, SCADAPack 3xx, SCADAPack 32 Product Status:known_affected Remediations MitigationImplement the Role-Based Access Control (RBAC) feature and follow the SCADAPack documentation sections Security Guidelines for Administrators and Working with Role-Based Access Control. RBAC is the recommended access control mechanism for SCADAPack 47x devices and should be used in place of the Secure Lock feature. The Secure Lock feature is legacy functionality retained for backward compatibility with existing deployments and should only be used where required to support legacy system requirements. Consult the SCADAPack Cybersecurity Guide, including the SCADAPack Hardening and Secured Communication sections. In addition, apply the following standard practices to reduce the risk of exploitation: Configure network segmentation to restrict access between trusted and untrusted networks. Enable and implement the RTU firewall service to restrict unauthorized access to device services and reduce the attack surface. Documentation available in RemoteConnect and SCADAPack x70 Utilities | Schneider Electric https://www.se.com/ww/en/download/document/RemoteConnect/ MitigationEnsure setup of network segmentation to restrict access between trusted and untrusted networks and implementation of the RTU Firewall Service to restrict unauthorized access to services. Consult the SCADAPack Cybersecurity Guide, including the SCADAPack Hardening and Secured Communication sections. In addition, implement all best practices referenced in the SCADAPack Cybersecurity Guide. Documentation available in RemoteConnect and SCADAPack x70 Utilities | Schneider Electric https://www.se.com/ww/en/download/document/RemoteConnect/ Mitigation For more information see the associated Schneider Electric security advisory SEVD-2026-251-03 Insufficiently Protected Credentials vulnerability on SCADAPack x70 Products PDF Version, CSAF Version. Relevant CWE: CWE-522 Insufficiently Protected Credentials Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N Acknowledgments Abhinav Agarwal reported this vulnerability to CISA. General Security Recommendations Schneider Electric strongly recommends the following industry cybersecurity best practices: Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. Place all controllers in locked cabinets and never leave them in the “Program” mode. Never connect programming software to any network other than the network intended for that device. Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. For More Information This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp LEGAL DISCLAIMER THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION About Schneider Electric Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and service
Indicators of Compromise
- cve — CVE-2026-81861