Yokogawa CENTUM VP contains hardcoded password vulnerability affecting manufacturing and energy sectors worldwide.

Summary

Yokogawa CENTUM VP versions R5.01.00–R5.04.20, R6.01.00–R6.12.00, and R7.01.00 contain a hardcoded password (CVE-2025-7741) for the PROG user account used in CENTUM Authentication Mode, allowing local attackers with HIS screen access to authenticate and potentially modify system permissions. The vulnerability has a CVSS score of 4.0 (Medium) and requires high attack complexity; it is not remotely exploitable. Mitigation involves switching to Windows Authentication Mode (R5/R6) or applying patch R7.01.10 (R7), and CISA recommends network isolation and VPN-based remote access for affected critical infrastructure.

Full text

ICS Advisory Yokogawa CENTUM VP Release DateApril 02, 2026 Alert CodeICSA-26-092-02 Related topics: Industrial Control System Vulnerabilities, Industrial Control Systems View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to login as the PROG user and modify permissions. The following versions of Yokogawa CENTUM VP are affected: CENTUM VP >=R5.01.00| CENTUM VP >=R6.01.00| CENTUM VP vR7.01.00 (CVE-2025-7741) CVSS Vendor Equipment Vulnerabilities v3 4 Yokogawa Yokogawa CENTUM VP Use of Hard-coded Password Background Critical Infrastructure Sectors: Critical Manufacturing, Energy, Food and Agriculture Countries/Areas Deployed: Worldwide Company Headquarters Location: Japan Vulnerabilities Expand All + CVE-2025-7741 Affected products contain a hardcoded password for the user account (PROG) used for CENTUM Authentication Mode within the system. Under the following conditions, there is a risk that an attacker could log in as the PROG user. The default permission for the PROG users is S1 permission (equivalent to OFFUSER). Therefore, for properly permission-controlled targets of operation and monitoring, even if an attacker logs in as the PROG user, the risk of critical operations or configuration changes being performed is considered low. If the PROG user's permissions have been changed for any reason, there is a risk that operations or configuration changes may be performed under the modified permissions. Additionally, exploiting this vulnerability requires an attacker to already have access to the HIS screen controls. View CVE Details Affected Products Yokogawa CENTUM VP Vendor:Yokogawa Product Version:Yokogawa CENTUM VP: >=R5.01.00|<R5.04.20, Yokogawa CENTUM VP: >=R6.01.00|<R6.12.00, Yokogawa CENTUM VP: vR7.01.00 Product Status:known_affected Remediations MitigationYokogawa recommends users applying the following mitigations to affected versions: Vendor fixCENTUM VP R5.01.00 to R5.04.20: Change the user authentication mode to Windows Authentication Mode. Vendor fixCENTUM VP R6.01.00 to R6.12.00: Change the user authentication mode to Windows Authentication Mode. Vendor fixCENTUM VP R7.01.00: Apply patch software R7.01.10. MitigationNOTE:Changing to Windows Authentication Mode requires engineering work. If users wish to make this change, please contact Yokogawa directly https://contact.yokogawa.com/cs/gw?c-id=000498.https://contact.yokogawa.com/cs/gw?c-id=000498 MitigationFor more information and details on implementing these mitigations, users should see the Yokogawa advisory YSAR-26-0003 at https://web-material3.yokogawa.com/1/39281/files/YSAR-26-0003-E.pdfhttps://web-material3.yokogawa.com/1/39281/files/YSAR-26-0003-E.pdf Relevant CWE: CWE-259 Use of Hard-coded Password Metrics CVSS Version Base Score Base Severity Vector String 3.1 4 MEDIUM CVSS:3.1/AV:L/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:N Acknowledgments Yokogawa reported this vulnerability to CISA Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely. This vulnerability has a high attack complexity. Revision History Initial Release Date: 2026-04-02 Date Revision Summary 2026-04-02 1 Initial Republication of YSAR-26-0003 Legal Notice and Terms of Use This product is provided subject to this Notification and this Privacy & Use policy. Vendor Yokogawa Tags Sector: Critical Manufacturing Sector, Energy Sector, Food and Agriculture Sector Topics: Industrial Control System Vulnerabilities, Industrial Control Systems Please share your thoughts We recently updated our anonymous product survey; we welcome your feedback. Related Advisories Apr 02, 2026 ICS Advisory | ICSA-26-092-01 Siemens SICAM 8 Products Apr 02, 2026 ICS Advisory | ICSA-26-092-03 Hitachi Energy Ellipse Mar 31, 2026 ICS Advisory | ICSA-26-090-01 Anritsu Remote Spectrum Monitor Mar 31, 2026 ICS Advisory | ICSA-26-090-02 PX4 Autopilot

Indicators of Compromise

  • cve — CVE-2025-7741

Entities

Yokogawa (vendor)CENTUM VP (product)Industrial Control Systems (technology)