Back to Feed
VulnerabilitiesSep 3, 2026

Tycon Systems TPDIN-Monitor-WEB3

Tycon Systems TPDIN-Monitor-WEB3 firmware versions <=2.2.9 have multiple vulnerabilities.

Summary

Multiple vulnerabilities have been identified in Tycon Systems TPDIN-Monitor-WEB3 firmware versions 2.2.9 and prior. These include hard-coded credentials, cross-site request forgery (CSRF), and missing authorization. Successful exploitation could lead to man-in-the-middle attacks, factory resets, credential wiping, or sensitive information retrieval. Tycon Systems has released firmware version 2.4.2 to address these issues.

Full text

ICS Advisory Tycon Systems TPDIN-Monitor-WEB3 Release DateSeptember 03, 2026 Alert CodeICSA-26-246-08 Related topics: Industrial Control System Vulnerabilities , Industrial Control Systems View CSAF Summary Successful exploitation of these vulnerabilities could allow for an attacker to perform a man-in-the-middle (MitM) attack, cause a factory reset, wipe credentials, or retrieve sensitive information. The following versions of Tycon Systems TPDIN-Monitor-WEB3 are affected: TPDIN-Monitor-WEB3 <=2.2.9 (CVE-2026-77847, CVE-2026-82712, CVE-2026-82684) CVSS Vendor Equipment Vulnerabilities v3 8.8 Tycon Systems Tycon Systems TPDIN-Monitor-WEB3 Use of Hard-coded Credentials, Cross-Site Request Forgery (CSRF), Missing Authorization Background Critical Infrastructure Sectors: Critical Manufacturing, Energy Countries/Areas Deployed: Worldwide Company Headquarters Location: United States Vulnerabilities Expand All + CVE-2026-77847 Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Use of Hard-coded Credential vulnerability. This could allow an attacker to intercept sensitive information or credentials. View CVE Details Affected Products Tycon Systems TPDIN-Monitor-WEB3 Vendor:Tycon Systems Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9 Product Status:known_affected Remediations Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2. MitigationUnits already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs. MitigationFor more information, contact Tycon Systems: https://www.tyconsystems.com/contact Relevant CWE: CWE-798 Use of Hard-coded Credentials Metrics CVSS Version Base Score Base Severity Vector String 3.1 6.5 MEDIUM CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N 4.0 7.1 HIGH CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N CVE-2026-82712 Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Cross-Site Request Forgery vulnerability. This could allow an attacker to perform state changing operations on the device. View CVE Details Affected Products Tycon Systems TPDIN-Monitor-WEB3 Vendor:Tycon Systems Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9 Product Status:known_affected Remediations Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2. MitigationUnits already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs. MitigationFor more information, contact Tycon Systems: https://www.tyconsystems.com/contact Relevant CWE: CWE-352 Cross-Site Request Forgery (CSRF) Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.8 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H 4.0 8.6 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N CVE-2026-82684 Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Missing Authorization vulnerability. This could allow an attacker to extract system credentials, configurations, or flash contents. View CVE Details Affected Products Tycon Systems TPDIN-Monitor-WEB3 Vendor:Tycon Systems Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9 Product Status:known_affected Remediations Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2. MitigationUnits already running v2.4.2, for subsequent updates (signed container): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX): https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs. MitigationFor more information, contact Tycon Systems: https://www.tyconsystems.com/contact Relevant CWE: CWE-862 Missing Authorization Metrics CVSS Version Base Score Base Severity Vector String 3.1 8.1 HIGH CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N 4.0 8.6 HIGH CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N Acknowledgments Abdiwelli Guled reported these vulnerabilities to CISA. Legal Notice and Terms of Use This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy). Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-09-03 Date Revision Summary 2026-09-03 1 Initial Publication Legal Notice and Terms of Use This product is provided subject to this Notification and this Privacy & Use policy. Tags Sector: Critical Manufacturing Sector, Energy Sector Topics: Industrial Co

Indicators of Compromise

  • cve — CVE-2026-77847
  • cve — CVE-2026-82712
  • cve — CVE-2026-82684

Entities

TPDIN-Monitor-WEB3 (product)Tycon Systems (vendor)